Operation Triple Plus+ and Triple Plus+ IR
level by pressing the UNMARKED button. The peak gas level will
then be displayed again from then on.
In addition to the messages described above, if alarms are muted the message
‘MUTED’ will flash with the sensor name and units.
2.3 Overrange
If a flammable sensor’s signal is out of range then the instrument may be
configured, via a PC and the Portables PC software, to either flash the relevant
numbers on the display, or to display a message of the form 'SENSOR FAILURE'
and the name of the failed sensor. The alarm sounder will activate. This type
of error could indicate a high gas level or sensor failure. Calibration should be
checked after such a warning.
2.4 Cautions
Sensors may be adversely affected by exposure to silicones, lead compounds,
high levels of hydrogen sulphide and chlorine, and some industrial solvents.
A condition of certification is that the instrument is not used with ethyl nitrate
vapours, or in hazardous areas containing IIC gases (e.g. hydrogen, acetylene)
where the risk of mechanical damage to the enclosure is high.
2.5 Backlight
In low ambient light conditions, the backlight can be activated to illuminate the
display by pressing the BACKLIGHT button. To switch off the backlight press the
BACKLIGHT button again, or it will turn off automatically after a configurable
timeout period of 10, 20 or 30 minutes. Alternatively, the backlight may be
configured to remain on permanently, or to never timeout once switched on.
(See LIGHT in section 3.2, Configuration Options). In an alarm condition, the
backlight is automatically turned on.
2.6 Alarms
When the Triple Plus+/Plus+ IR encounters an alarm condition the red lights
flash, the beacons activate and the sounder emits a loud, fast bleep. Where
permitted instantaneous toxic gas alarms may be accepted by pressing the
UNMARKED button. In this case, the sounder is silenced but the red lights
continue to flash. With instantaneous alarms, the word 'ALARM' will flash
next to the gas name. Time Weighted Average exposure limit alarms will flash